Conductivity Analog Controller - Available in four models with different measurement ranges
- Single set point with user-selectable dosage
- Recorder output
These instruments have to be used in conjunction with the HI 8936 transmitters series sold separately. Thanks to this installation it is possible to receive a signal without any noise from a distance of up to 300 meters from the measuring point. The dosing type is selectable through a jumper on the rear panel. Four different models are available with different measurement ranges, each one to be used with the corresponding HI 8936 model. The output configuration for connecting a recorder or a PLC can be chosen between 0-20 or 4-20 mA. The front panel is protected behind a transparent splash-proof cover.
The HI 8931 series is supplied complete with mounting brackets and instructions. |
|
|
Range | HI 8931A, D: 0.0 to 199.9; HI 8931B: 0.00 to 19.99 | Accuracy (@20°C/68°F) | ±2% of F.S. | 4-20 mA Input | HI 8936A, B, C, D | Readout | 4-digit LCD plus graphic symbols | Recorder Output | 0 to 20 mA or 4 to 20 mA (not isolated) | 1 Set Point Relay | Isolated, 2A, Max. 240V, resistive load, 1,000,000 | 1 Alarm Relay | Isolated, 2A, Max. 240V, resistive load, 1,000,000 | Battery Type / Life | 110/115V; 50/60 Hz or 220/240V; 50/60 Hz | Environment | 14 to 122°F (-10 to 50°C) | Dimensions | DIN 43 700 5.7 x 2.8" (144 x 72mm) | Weight | 2.2 lbs. (1Kg) | Panel Cutout | 5.6 X 2.7" (141 x 69 mm) |
|
|